 Current Transducers HTB 50 .. 400-P/SP5 and HTB 50 .. 100-TP/SP5
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 50 .. 400 A
Electrical data
Primary nominal r.m.s. current IPN (A) 50 100 200 300 400 Primary current measuring range IP (A) 150 300 500 600 600 Type
HTB 50-P/SP5, HTB 50-TP/SP51) HTB 100-P/SP5, HTB 100-TP/SP51) HTB 200-P/SP5 HTB 300-P/SP5 HTB 400-P/SP5
Features
* Hall effect measuring principle * Galvanic isolation between primary * Isolation voltage 2500V * Low power consumption * Primary bus bar option for 50A and
100A version for ease of connection and secondary circuit
VC IC Vd R IS VOUT ROUT RL
Supply voltage (5 %)2) Current consumption R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn Isolation resistance @ 500 VDC Output voltage @ IPN, RL = 10 k, TA = 25C Output internal resistance Load resistance
+12 .. +15 V <15 mA 2.5 kV >500 M VOE 1.667 V 100 10 k
Accuracy - Dynamic performance data
Special Features
* Single power supply from 12V to 15V
X
L
VOE VOH VOT TC G tr f
Accuracy @ IPN, TA = 25C (without offset) <1 % of IPN Linearity (0 .. IPN) <1 % of IPN Electrical offset voltage, TA = 25C Vc/230 mV Hysteresis offset voltage @ IP = 0; after an excursion of 3 x IPN <0.5 % of IPN Thermal drift of VOE HTB 50-(T)P/SP5 <1.0 mV/K HTB 100-(T)P..400-P/SP5 <0.5 mV/K Thermal drift (% of reading) <0.05 %/K Response time @ 90% of IP <3 s Frequency bandwidth (-3 dB)3) DC .. 50 kHz
Advantages
* Small size and space saving * Only one design for wide current * High immunity to external
interference. ratings range
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass (-TP version) -25 .. +85 -25 .. +85 <30 (<36) C C g
Applications
* AC variable speed drives * Static converters for DC motor drives * Battery supplied applications * Uninterruptible Power Supplies * Switched Mode Power Supplies
(UPS) (SMPS)
Notes : EN 50178 approval pending 1) -TP version is equipped with a primary bus bar. 2) Operating at +12V Vc < +15V will reduce measuring range. 3) Derating is needed to avoid excessive core heating at high frequency.
* Power supplies for welding
applications.
030221/0
LEM Components
www.lem.com
HTB 50 ... 400-P/SP5
Back view
39 14 MAX.
Left view
Positive Current Flow
34
d1
6
1.5
19.5
4-0.635x0.635 3
24.5 5.5
3.5
32 1
Secondary Pin Identification
2-d2 Mounting Pins 7 11
2-P=2.5 6 +/-1
9 +/-1
1 +Vc 2 0V 3 Output
Bottom View
10
19
3
HTB 50 ... 100-TP/SP5
Back view
39 14 MAX.
3
Left view
34
1.5
17
4-0.635x0.635 3
10
2-P=2.5 10.5 3 3 9 2 3.25
3.5
321
1.5 1.5
3.5
1.5
Positive Current Flow
6-1.5x1.5
Secondary Pin Identification 1 +Vc 2 0V 3 Output
14
3
Bottom view
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
3
11


▲Up To Search▲   

 
Price & Availability of HTB200-PSP5

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X